PRODUCTS
1. THREE PHASE ELECTRONIC ENERGY METERS
|
STANDARDS
|
: |
Conforms to IS 13779, IS 14697, IEC 62052/62053 & CBIP Report No. 88
|
ACCURACY
|
: |
Class 1.0 & 0.5 S
|
NOMINAL VOLTAGE
|
: |
3 x 240 Volts AC, Variation + 20% to - 40%
|
MAXIMUM CURRENT
|
: |
20A, 30A, 40A & 60A for Whole Current Meters &
120% of Ib for CT Operated Meters
|
NOMINAL FREQUENCY
|
: |
50 Hz +/- 5%
|
DISPLAY
|
: |
6 digits electromechanical stepper motor register or
LCD display
|
ANTI TAMPER FEATURES :
|
|
o |
Meter records correct energy under reverse current connection.
|
|
o |
Meter records energy correctly even in the absence of Neutral.
|
|
o |
No effect of external magnetic field as per CBIP 88
|
|
o |
Meter works correctly irrespective of the phase sequence.
|
|
o |
Immunity to D.C. component in A. C. circuit
|
|
o |
Meter works even if only two phases or one phase & neutral are present.
|
|
o |
Power on indication by Three LED's one for each phase.
|
|
o |
Meter Base & Cover are provided for Ultrasonic Welding.
|
OPTIONAL FEATURES :
|
|
o |
Single wire operation
|
|
o |
Real Time
|
|
o |
Instantaneous Parameters like Voltage, Current, Load, Power Factor, Frequency etc.
|
|
o |
Maximum Demand
|
|
o |
TOD Metering
|
|
o |
RS 232/485 communication
|
2. SINGLE PHASE ELECTRONIC ENERGY METERS
|
STANDARDS
|
: |
Conforms to IS 13779, IEC 62052/62053 &
CBIP Report No. 88
|
ACCURACY
|
: |
Class 1.0
|
NOMINAL VOLTAGE
|
: |
240 Volts, 1 Phase, Variation + 20% to - 40%
|
MAXIMUM CURRENT
|
: |
10A, 20A, 30A, 40A & 60A
|
NOMINAL FREQUENCY
|
: |
50 Hz +/- 5%
|
DISPLAY
|
: |
6 digits electromechanical stepper motor register or
LCD display
|
ANTI TAMPER FEATURES :
|
|
o |
Meter functions correctly when phase & neutral are interchanged.
|
|
o |
Meter records correct energy under reverse current connection.
|
|
o |
Meter records correct energy when load is connected to earth instead of neutral.
|
|
o |
No effect of external magnetic field as per CBIP 88 |
|
o |
Immunity to D.C. component in A. C. circuit
|
|
o |
Tamper condition is indicated through LED's
|
|
o |
Meter Base & Cover are provided for Ultrasonic Welding.
|
OPTIONAL FEATURES :
|
|
o |
Single wire operation
|
|
o |
Real Time
|
|
o |
Instantaneous Parameters like Voltage, Current, Load, Power Factor, Frequency etc.
|
|
o |
Maximum Demand
|
|
o |
TOD Metering
|
|
o |
RS 232/485 communication
|
3. SINGLE PHASE HIGH PRECISION ELECTROMECHANICAL ENERGY METERS
|
STANDARDS
|
: |
Conforms to IS 13010, IEC 521 & CBIP Report No.88
|
ACCURACY
|
: |
Class 2.0
|
NOMINAL VOLTAGE
|
: |
240 Volts, 1 Phase, Variation + 20% to - 40%
|
MAXIMUM CURRENT
|
: |
5A, 10A, 20A, 30A & 40A
|
NOMINAL FREQUENCY
|
: |
50 Hz +/- 5%
|
REGISTERING MECHANISM
|
: |
Cyclometer type with 5/6 drums. The unidirectional counters are also available
|
BRAKE MAGNET
|
: |
Four pole magnet of ALNICO Grade V or VI. The
magnets are aged against time, temp. & external
magnetic effects before assembly
|
LOWER BEARING
|
: |
Magnetic suspension type with two homo polar
annular magnets with a guide & bearing bush.
|
STARTING CURRENT
|
: |
0.5% of Ib at rated voltage & unity power factor
|
TORQUE
|
: |
More than 4.0 gm-cm at Ib
|
VOLTAGE CIRCUIT POWER LOSS
|
: |
As per IS : 13010-2002
|
AC VOLTAGE TEST
|
: |
4 KV for 1 minute
|
ADJUSTMENTS :
|
|
o |
Full load adjustment
|
|
o |
Low load adjustment
|
|
o |
Inductive load adjustment
|
|
o |
Creep adjustment
|
EFFICIENCY FACTOR
|
: |
1.2 minimum
|
4. THREE PHASE HIGH PRECISION ELECTROMECHANICAL ENERGY METERS
|
STANDARDS
|
: |
Conforms to IS 13010, IEC 521 & CBIP Report No.88
|
ACCURACY
|
: |
Class 2.0 for Whole Current Meters & Class 1.0 &
2.0 for CT Operated Meters
|
NOMINAL VOLTAGE
|
: |
3 x 240 Volts, Variation + 20% to - 40%
|
MAXIMUM CURRENT
|
: |
5A, 10A, 20A, 30A & 40A for Whole Current Meters
& 120% of Ib for CT Operated Meters
|
NOMINAL FREQUENCY
|
: |
50 Hz +/- 5%
|
REGISTERING MECHANISM
|
: |
Cyclometer type with 5/6 drums. The unidirectional counters are also available
|
BRAKE MAGNET
|
: |
Four pole magnet of ALNICO Grade V or VI. The
magnets are aged against time, temp. & external
magnetic effects before assembly
|
LOWER BEARING
|
: |
Magnetic suspension type with two homo polar
annular magnets with a guide & bearing bush.
|
STARTING CURRENT
|
: |
0.5% of Ib at rated voltage & unity power factor
|
TORQUE
|
: |
More than 8.0 gm-cm at Ib
|
VOLTAGE CIRCUIT POWER LOSS
|
: |
As per IS : 13010-2002
|
AC VOLTAGE TEST
|
: |
4 KV for 1 minute
|
ADJUSTMENTS :
|
|
o |
Full load adjustment
|
|
o |
Low load adjustment
|
|
o |
Inductive load adjustment
|
|
o |
Creep adjustment
|
|
o |
Torque adjustment
|
EFFICIENCY FACTOR
|
: |
1.2 minimum
|